Free calculator
Humidifier sizing calculator
A humidifier isn't filling the room once — it's replacing the moisture that every air exchange carries away. The output you need scales with room volume, the RH gap, and how leaky the space is.
Room & setpoint
Result
Room volume 800 ft³ (22.7 m³)
Output to hold 65% RH
3.1L/day= 0.8 gal/day
One-time charge to raise the air
130mL
Tiny compared to the ongoing load — leakage is the real bill.
Shop for a unit rated ~20% above this (3.8 L/day) so it can cycle rather than run flat out — and expect transpiring plants to shrink the load as the canopy fills in.
Assumes make-up air enters at room temperature and your current RH. In winter, infiltrating air is colder and much drier once heated, so real demand runs higher than this estimate — size up if you heat.
Chasing an RH number? What actually matters is VPD — calculate it here →